Title of Invention

METHOD AND APPARATUS FOR CHARACTERISING A THREE PHASE TRANSFORMER USING A SINGLE PHASE POWER SUPPLY

Abstract A method and apparatus for characterising a three phase transformer (3) using a single phase power supply (1). Pairs of input terminals (H0-H3) of the transformer are sequentially energised for each energisation and the voltage between pairs of output terminals (x0-x3) of the transformer are measured. Measured voltages are processed in order to characterise the winding configuration of the transformer. Either simultaneously or subsequently the presence of neutrals on the primary and/or secondary side of the transformer are identified to enable the winding configuration to be further characterised. Subsequently any phase displacement of the transformer is determined. The apparatus comprises means (2) for selectively applying a single phase power supply (1) to pairs of terminals (H0-H3) on the transformer (3) and for measuring voltages between pairs of terminals (x0-x3) of the transformer and for measuring phase difference between the primary and secondary sides of the transformer all under automatic control of a control means (13) which includes a processing means to process measured voltages and phase differences in order to characterise the transformer.
Full Text

The present invention relates to a method and apparatus for characterising a
three phase transformer using a single phase power supply.
Three phase transformers are widely used in power supply and other
applications. They typically comprise primary and secondary windings for each
phase mounted on a three legged core.
The turns ratio of a transformer is the ratio of the number of turns of its
primary winding divided by the number of turns of the secondary winding, for each
leg of the transformer. The turns ratio is equivalent to the step up or step down
voltage ratio of the transformer. By measuring the turns ratio of a transformer from
its performance and comparing this with its rated voltage a good indication of the
condition of the transformer can be obtained.
Transformers are routinely tested in this way throughout their life. Typically
testing is carried out after manufacture to ensure that the. transformer has been
correctly wound, similarly after refurbishment or remanufacture, and as part of
ongoing maintenance in order to detect any degradation in performance.
Probably the simplest way to measure the rums ratio of a three phase
transformer, at least from the point of view of the apparatus required, is to use a single
phase power supply to test the three pairs of primary and secondary windings
individually. This approach is particularly desirable for field testing where providing
a single phase power supply for testing is easier than providing a three phase supply,
In fact provision of an appropriate three phase power supply may be impossible.
A drawback with use of a single phase supply to measure the turns ratio of a

three phase transformer is that the way voltage should be applied to the transformer
and the way it should be measured depends on characteristics of the transformer being
tested, particularly its configuration and phase displacement, if any
The primary and secondary windings of a three phase transformer can each be
connected in one of five known configurations D (Delta), Y (Wye), Yn, Z (Zig Zag)
and Zn.
In D configuration three windings are connected end to end in a loop and three
external connections for the transformer are taken from between the windings. In Y
configuration (also known as star configuration) one end of each winding are all
connected together. The free ends of each winding form three external connections.
In Yn configuration the connection between the three windings of a Y configuration is
brought out as an additional neutral connection. Z configuration is electrically the
same as Y, but each winding is distributed across more than one leg of the transformer
to improve performance in the presence of an unbalanced load. Zn is a Z
configuration with the connection between the windings brought out as neutral.
A three phase transformer can have a phase displacement. Shifting the
secondary connections with respect to the primary connections, essentially re-
labelling the connections, introduces a phase shift in 60 degree steps, as can reversing
the windings. Configuration of the windings also affects phase. If configurations of
the primary and second side are dissimilar an additional 30 degree shift is introduced.
Phase displacement is usually classified using a number between 0 and 11 to indicate
the number of 30 degree steps from in phase introduced by the transformer.
Before the turns ratio of a transformer can be properly measured using a single

phase power supply it is necessary to know the winding configuration and any phase
displacement of the transformer.
It is an object of the present invention to enable the windings configuration
and/or phase displacement of a three phase transformer to be determined using a
single phase power supply. It is a particular object to enable winding configuration
and/or phase displacement to be automatically determined.
According to a first aspect of the present invention, there is provided a method
of characterising a three phase transformer having three input terminals and three
output terminals using a single phase power supply, the method comprising the steps
of:
sequentially connecting the single phase power supply between all three
available pairs of input terminals selected from the three input terminals of the
transformer so as to energise each available pair of input terminals in turn;
during energisation of each pair of terminals measuring the voltage between
all three available pairs of output terminals selected from the three output terminals of
the transformer; and
processing the measured voltages to characterise the transformer.
According to a second aspect of the present invention, there is provided
apparatus for characterising a three phase transformer using the method of the first
aspect of the present invention.
When characteristics of the transformer have been determined, it is possible
for the turns ratio of the transformer to be measured using a single phase power
supply.

Preferably, the method and apparatus enable a three phase transformer to be
characterised according to its winding configuration. The method and apparatus may
classify a three phase transformer as either D-D equivalent, D-Y equivalent, Y-D
equivalent or Y-Y equivalent. The method and apparatus may further classify a
transformer according to the presence of a neutral on either the primary or secondary
side of the transformer, thereby to further characterise its winding configuration.
The method and apparatus also preferably enables the phase displacement of a
transformer to be characterised.
The apparatus preferably comprises a single phase power supply and means
for selectively applying power from the power supply to pairs of input terminals of a
three phase transformer. Said means may comprise a switching matrix. The
apparatus preferably further comprises means for measuring voltage between pairs of
output terminals of a three phase transformer, which means may also include a
switching matrix. The apparatus may further include a phase meter. The various
components of the apparatus are preferably under the control of a control means
which may comprise a programmed computer. The control means preferably
includes a processing means for processing measured voltages in order to determine
characteristics of the transformer. The apparatus may further include means for
shorting any two terminals of a transformer together. Such means may comprise a
shorting matrix.
The apparatus is preferably arranged to automatically characterise a
transformer and provide results to a user. The apparatus may be further arranged to
automatically test the turns ratio of a transformer using the single phase power supply,

by the application of a known method.
The apparatus is preferably self contained and portable to facilitate in the field
testing of transformers. The power supply of the apparatus may be provided by a local
mains power supply.
In order that the invention may be more clearly understood an embodiment
thereof will now be described, by way of example, with reference to the
accompanying drawings of which:
Figure 1 is a schematic diagram of apparatus according to the invention;
Figure 2 is a flowchart illustrating operation of the apparatus of Figure 1; and
Figure 3 is another flowchart illustrating further operation of the apparatus of
Figure 1.
An embodiment of the invention will be described with reference to a notional
three phase transformer to be tested having input (primary) terminals H1, H2, H3 and
optionally an input neutral terminal HO, and output (secondary) terminals X1, X2, X3
and optionally an output neutral terminal XO.
First the winding configuration of a transformer to be tested is determined.
Because the primary and secondary windings of a three phase transformer can
each be wound in five ways there are a total of twenty five possible configurations for
a transformer, as set out below, however it is unlikely to find all these configurations
in practice.



Single-phase energisation of a transformer with-aZ configuration produces the
same results as a D configuration, so it is impossible to distinguish between the two,
The use of Z windings on the primary of a transformer is unusual so these are treated
as a special case. Because of the equivalent behaviour of Z and D windings, they are
defined as similar, with Y windings being treated as different. This gives two groups
of winding configurations:
D - Z - Zn; and
Y -Yn
This allows transformers to be grouped into four groups depending on the
configuration of their primary and secondary windings, as set out below.

Energising a transformer input to input on the primary side and measuring the
output to output voltages obtained on the secondary side allows a discrimination of
the transformer's class to be made. The transformer is energised H1-H3, H2-H1 and

H3-H2 and with each energisation the line-to-line voltages X1-X3, X2-X1 and X3-X2
are measured. Each set of three secondary measurements is normalised to the highest
line-to-line voltage measured for that energisation. The theoretical results expected for
transformers of each group identified above are as follows:

This shows that four response patterns can be expected to be observed, which can be
classified as follows:
Class Response
A 1:1:0
B 1:0.85:0.15
C 1:0.66:0.33
D 1:0.5:0.5
The responses of the four groups of transformers can be further classified according to
the classes of response that they show thus:
Group 1 (D-D) = (2 * Class B) + (1 * Class D)
Group 2 (D-Y) = (2 * Class C) + (1 * Class A)

Group 3 (Y-D) = (2 * Class B) + (1 * Class A)
Group 4 (Y-Y) = (2 * Class C) + (1 * Class D)
So, by determining the class of response under each of the possible line-to-line
energisations, it is possible to determine the group of the transformer under test. The
expected voltage values shown above are theoretical ideal values and may not be seen
in practice. Therefore to classify transformers in practice a range of values is
substituted for each expected value and measured voltages are classified according to
the range in which they fall.
Once the class of the transformer has been determined, it is necessary to
determine if it has neutral connections. If there is no neutral connection, there is
essentially a floating connection. The presence of a primary neutral can be
determined by comparing the voltage produced on the secondary measuring output to
output when the primary is energised input to input and input to neutral. If there is a
significant difference recorded it indicates that the neutral line is floating (i.e. not
connected). A similar process can be followed to determine the presence of a neutral
on the secondary side. The transformer is energised input to input on the primary and
the output to output and output to neutral voltages on the secondary are compared.
Again if there is a significant difference, it indicates that the neutral line is floating
(i.e. not connected).
When the group of transformer and the presence or absence of primary and
secondary neutral connections is known, it is possible to determine the winding
configuration:



Once the configuration of a transformer has been determined, it is possible to
determine its phase displacement. A three phase transformer core can be considered as
having three legs A, B and C, each of which carries a primary and a secondary
winding. If we regard the input to each primary winding as H1, H2 and H3 and the
output of each secondary winding as X1, X2 and X3 the phase displacement is
determined by which secondary outputs are on the same leg as which primary inputs.

At this stage it can also be helpful to determine if any output terminals are swapped
over with respect to the input terminals (e.g. X2 and X3 exchanged with respect to H2
and H3).
Determining which leg if a transformer is which depends on the class of the
windings. The transformer is energised across one phase with the other input terminal
shorted to the low end of the energising supply. This constrains the flux in the core of
the transformer, and produces a minimum or a maximum on one of the output phases
depending on the configuration of the transformer. By this process the phase shift,
cause by rotation of the output terminals with respect to the input terminals, is
determined. There are three possibilities: 0 (no phase shift), 4 (120 degrees) and 8
(240 degrees).
Transformers can be divided into two different classes for the determination of
the phase shift. Phase shift Class 1 transformers have similar primary and secondary
windings (i.e. Group 1 or Group 4 transformers) while Phase shift Class 2
transformers have dissimilar primary and secondary windings. This affects the way
the transformer is treated to determine the winding configuration:
Phase Shift Class 1 Energise leg A, short leg C, minimum is measured on leg C
Phase Shift Class 2 Energise leg A, short leg C, maximum is measured on leg B
So for each group of transformers one can determine the phase shift due to the
shifting of output terminals with respect to the input terminals (Note, "shifting"
indicates output terminals swapped with respect to input terminals, that is that the X2
and X3 connections are reversed, essentially swapping the phase rotation from
clockwise to anti-clockwise or vice versa.) The definition of which leg of the

transformer is A, B or C depends on the configuration of the transformer and how we
are energising it. If we define
A as energisation H1-H3, then leg a = X1-X3, leg b= X2-X1, leg c = X3-X2
A' as energisation H2-H1, then leg a' = X2-X1, leg b'= X3-X2, leg c' = X1-X3
A" as energisation H3-H2, then leg a" = X3-X2, leg b"= X1-X3, leg c" = X2-X1
So, for the two phase shift classes of transformers the following will be
observed.



By applying the appropriate energisation pattern, and looking for the
maximum or minimum depending on whether the windings are dissimilar or similar,
it is possible to determine the basic phase displacement of the transformer.
Once the phase shift has been determined, it is necessary to check for phase
reversal, where the polarity of the secondary winding is reversed with respect to the
primary winding, introducing a 180 degree phase shift onto the output. This is
achieved by energising one leg of the transformer and looking at the corresponding
secondary to see if the voltage is in phase with the energising voltage or 180 degrees
out of phase. The phases to be energised and measured depend on the shift as
determined previously:

A figure from 0 to 11 for the phase displacement of the transformer is then

calculated by taking the phase shift, if the windings are reversed adding 6 and if the
transformer is Class 2 adding 1. If the result is greater than 11, 12 is subtracted.
Figure 1 shows apparatus for automatically implementing the above method.
Referring to figure 1 the apparatus comprises various electrical components and
provides eight electrical test connections for connection to the terminals of a
transformer to be tested 3. The apparatus comprises an energisation source 1 which
provides a single phase electrical signal to a switching matrix 2. A switching matrix 2
is connected to each of the four test connections for connection to terminals H0-3 of a
transformer under test 3. A second switching matrix 6 is also connected to each of the
four connections and a shorting matrix 4 is connected to the connections intended for
terminals H1-3 of a transformer under test 3. A third switching matrix 7 is connected
to each of the four connections for connection to terminals XO-3 of a transformer
under test 3 and a second shorting matrix 7 is connected the connections intended for
terminals X1-3 of a transformer under test 3. The second 6 and third 7 switching
matrices are connected via respective 3rd harmonic filters 8, 9 to respective voltmeters
10, 11 and a single phasemeter 12
The various electrical components of the apparatus described above are all
under control of a control unit 13.
The energisation source 1 comprises a single-phase transformer driven from
the local mains electricity supply. However, alternative generation methods can be
utilised. It is important that the energisation source provides a substantially sinusoidal
signal as the presence of harmonics will disrupt measurement of the turns-ratio and
compromise the accuracy of the system.
The first switching matrix 2 allows the output of the energisation source 1 to
be applied, under the control of the control unit 13, across any two of the inputs H0-3
of the transformer under test 3.
The shorting matrix 4 is, in use, connected to H1, H2 and H3 of the
transformer under test 3 and allows the apparatus to short any two of the primary
terminals Hl-3 together. This is required for phase displacement determination.
The second shorting matrix 5 allows any two of the secondary phase terminals
X1, X2 and X3 of the transformer under test 3 to be shorted together. This feature is

not utilised for the winding configuration and phase determination procedure, but is
essential for subsequent turns-ratio measurement.
The second switching matrix 6 is operative to connect any of the primary
connections of the transformer under test 3, H0-3 to the voltmeter 10 and phasemeter
12. It is operated in synchronisation with the switching matrix 2 by the control means
13 so that the primary voltage at the terminals of the transformer is measured while
compensating for voltage drops in the measurement cables.
The third switching matrix 7 is operative to connect any two of the secondary
terminals of the transformer under test 3, X0-3 to the voltmeter 11 and phasemeter 12.
The third switching matrix 7 is operated by the control means 13 independently of the
first and second switching matrices 2,6.
The two 3rd harmonic filters 8 provide a notch response with a minimum at
either 150Hz or 180Hz depending on the line frequency selected. They eliminate a
third harmonic generated by the energisation source 1, or a transformer under test 3,
that could otherwise affect measurement
Voltages at the primary side of a transformer under test are measured by
voltmeter 10 by measuring the peak-to-peak: excursion of the primary waveform. The
waveform is constantly sampled by an ADC (analogue to digital converter), and a
digital peak detection system which returns the maximum and the minimum voltage
recorded by the ADC. The difference between the two is used as a measure of the
voltage. This automatically compensates for any DC offset on the measurement
channel. Voltages at the secondary side of a transformer under test are measured by
voltmeter 11 using the same technique.
The period of the voltage measured by voltmeter 10, the primary voltage, and
the time displacement between primary voltage zero crossings and zero crossings of
the voltage measured by voltmeter 11 (the secondary voltage) are measured by the
phasemeter 12, to determine the phase relationship between the primary and
secondary voltage to be measured by the apparatus.
The control means 13 comprises a software controlled computer, for example
a PC, and is operative, to control the various components of the apparatus in order to
determine the configuration and phase displacement of a transformer under test 3.

The control means 13 includes a processing means and a memory operative to store
values relating to measured voltages, constants and to perform calculations and output
results to a user in order to implement the algorithms described below. Any other
appropriate type of control means could of course be employed.
The software is first arranged to cause the apparatus to characterise the
configuration of the transformer under test by employing an algorithm illustrated in
figure 2, and then to further characterise the winding configuration and determine the
phase displacement by employing the algorithm illustrated in figure 3.
Referring to figure 2 the first stage is energising the transformer input to input
in each of the possible configurations (H1-H3, H2-H1 and H3-H2) and measuring the
output to output voltages in each configuration (X1-X3, X2-X1, X3-X2). For each
phase energisation, three measurements result, which must be classified to establish
the configuration.
Classification is achieved by sorting the three measurements for each phase-
to-phase energisation into order, so Vh is the highest, Vi is the intermediate value and
V1 is the lowest value. The three values are then combined to give a single figure of
merit:
FM = (Vi-V1)/Vh
This gives a classification value for each of the four class responses.
Theoretically these values are as follows:
Class A: 1:1:0 FM=1
Class B: 1:0.85:0.15 FM = 0.7
Class C: 1:0.666:0.333 FM = 0.333
Class D: 1:0.5:0.5 FM = 0
Because actual values may deviate from these the control means is arranged to
compare values using magnitudes in order to allocate the figure to the appropriate
class. One way to allocate values is to move from one class to another at the point
where the percentage difference between the two is equal, so
If (FM > 0.82) Result = Class A
If (FM 0.45) Result = Class B
If (FM 0.16) Result = Class C

If (FM In practice, though there are variations from the ideal in the FM values
measured. Similar values cause the measured FM values to be lower than the ideal,
while dissimilar windings cause them to be elevated. This can cause errors in
determination, so a modified set of factors are used, as follows:
If (FM > 0.82) Result = Class A
If (FM 0.48) Result = Class B
If (FM 0.16) Result = Class C
If(FM When the three sets of results have been classified the configuration of the
transformer is determined. By assigning values to each of the class results, the group
of the transformer is determined by summing the result values for each class result.
The constants are defined so that when three class results are summed, if they are the
same, they cannot be confused with a different class result. In this embodiment the
constants are defined as follows, although other definitions are possible.
Class A = 0x40 (64 decimal)
Class B = 0x 10 (16 decimal)
Class C = 0x04 (4 decimal)
Class D = 0x01 (1 decimal)
So, summing the results for each of the possible groups gives the following
results:
Group 1 (D-D) = (2 * 0x10) + 0x01 - 0x21 (33 decimal)
Group 2 (D-Y) = (2 * 0x04) + 0x40 = 0x48 (72 decimal)
Group 3 (Y-D) = (2 * 0x10) + 0x40 = 0x60 (96 decimal)
Group 4 (Y-Y) = (2 * 0x04) + 0x01 = 0x09 (9 decimal)
In other embodiments different methods of classification are used, for example
the use of a neutral network.
Once the transformer group has been determined it is necessary to determine
the presence of neutrals on the transformers, using the algorithm illustrated in figure
2. The transformer is energised using H1-H3, and X1-X3, X2-X1 and X3-X2, are
measured. The highest value is saved as Xpp. The transformer is then energised using

H1-H3 and X1-XO, X2-X0 and X3-X0 are measured. The highest value is saved as
Xpn. The transformer is finally energised using H1-H0 and X1-X3, X2-X1 and X3-X2
are measured. The highest value is saved as Xnp.
If Xpn/Xpp > 0.25 the transformer has a neutral on the secondary
If Xnp/Xpp > 0.25 the transformer has a neutral on the primary.
So there is enough information to determine the configuration of transformer:


If the time taken to determine the configuration is critical, some of the
measurements could be combined with the first stage of the determination process,
though this would add complexity to the implementation of the system.
The final stage of the process is to determine the phase displacement of the
transformer. The algorithm for this is also illustrated in the flow chart in figure 2. As
discussed above, there are three stages to determining the phase displacement of the
transformer. If the transformer has dissimilar windings an intrinsic 30-degree phase
shift introduced. This adds one to the determined phase displacement.
Looking at the tables above showing how the basic displacement of the
transformer is determined, we can arrange the results to give the same outputs for
either class of transformer:

So, depending on whether the transformer is class 1 or class 2 it is energised
using the patterns above and the terminals on the secondary that give the minimum
(class 1) or maximum (class 2). The leg results (highest or lowest leg) can be
combined to give a net result for the transformer, by assigning a constant to them and
summing the results:




The final stage is to determine if the windings are reversed. The transformer is
energised phase to phase on the primary and the corresponding phase to phase
measurement is made on the secondary. The phase shift of the secondary with respect
to the primary is measured. If it is greater than 90 degrees or less than -90 degrees, the
windings are reversed. The energisation and measurement phases are determined
using the following table:

The phase displacement is then be calculated using the following steps:
Are the Primary and Secondary Windings Similar? (Stage 1)
If Yes: Phase Displacement = 0
If No: Phase Displacement = 1
What is the Configuration result factor? (Stage 2)
0x24 = 36: Add 0 to Phase Displacement
0x12 =18: Add 4 to Phase Displacement
0x09 = 9: Add 8 to Phase Displacement
0x21 = 33: Add 0 to Phase Displacement
0x06 = 6: Add 4 to Phase Displacement
0x18 = 24: Add 8 to Phase Displacement
Are the secondary windings reversed? (Stage 3)
If Yes: Add 6 to the Phase Displacement

If No: Add 0 to the Phase Displacement
If the result is greater than 12, subtract 12 from the result.
The characteristics of the transformer being tested are now known and the
apparatus can be arranged to measure the turns ratio for the transformer using a single
phase power supply using a known method.
The above embodiment is described by way of example. Many variations are
possible without departing from the scope of the following claims.

We claim:
1. A method of characterising a three phase transformer having three input terminals and
three output terminals using a single phase power supply, the method comprising the steps of:
sequentially connecting the single phase power supply between all three available
pairs of input terminals selected from the three input terminals of the transformer so as to
energise each available pair of input terminals in turn;
during energisation of each pair of terminals measuring the voltage between all three
available pairs of output terminals selected from the three output terminals of the transformer;
and
processing the measured voltages to characterise the transformer.
2. A method as claimed in claim 1, wherein the measured voltages are processed to
characterise the transformer according to its winding configuration.
3. A method as claimed in claim 2, wherein the transformer is classified as D-D
equivalent, D-Y equivalent, Y-D equivalent or Y-Y equivalent.
4. A method as claimed in any preceding claim, wherein the three voltages measured
during energisation of each pair of input terminals are processed to identify the highest,
lowest and intermediate value and the difference between the intermediate value less the
lowest value computed and then divided by the highest value to produce three figures of
merit, one associated with energisation of each pair of input terminals.
5. A method as claimed in claim 4, wherein each figure of merit is classified into one of
four classes according to its value.
6. A method as claimed in claim 5, wherein each figure of merit is classified in a first
class if it is greater than 0.82, a second class if it is less than or equal to 0.82 but greater than
0.45, a third class if it is less than or equal to 0.45 but greater than 0.16 and a fourth class if it
is less than or equal to 0.16.
7. A method as claimed in claim 5 or 6, wherein a value is allocated to each figure of

merit according to its classification, the allocated values are then added, and the transformer
classified as D-D equivalent, D-Y equivalent, Y-D equivalent or Y-Y equivalent according to
the total.
8. A method as claimed in claim 7, wherein the first, second, third and fourth classes are
allocated the decimal numbers 64, 16, 4 and 1 respectively, (or equivalent numbers in a
different base) and the transformer classified as follows according to the total of the allocated
values:

9. A method as claimed in any preceding claim, wherein the transformer is characterised
according to the presence of neutrals on its primary and/or secondary side.
10. A method as claimed in claim 9, wherein the transformer has three input terminals H1,
H2 and H3 and an input neutral terminal HO and three output terminals X1, X2 and X3 and
an output neutral X0 and when the single phase power supply is connected between input
terminals H1 and H3 the highest voltage measured between output terminals X1 and X3, X2
and X1 and X3 and X2 is saved (Xpp) and the highest voltage measured between X1 and X0,
X2 and X0 and X3 and X0 is saved (Xpn) and further comprising the step of connecting the
single phase power supply between H1 and HO, measuring the voltages between X1 and X3,
X2 and X1, and X3 and X2, saving the highest value (Xnp) and determining the ratios of the
first saved voltage with each of the second and third saved voltages respectively (Xp„/Xpp and
Xnp /Xpp) thereby to determine the presence of neutrals on the primary and/or secondary side of
the transformer.
11. A method as claimed in claim 10, when dependent directly or indirectly on claim 3
wherein the presence or absence of a neutrals is combined with the classification of winding
configuration in order to further classify the winding configuration of the transformer as one

of the following:
a) D-D or D-Z or Z-D or Z-Z
b) D-Zn
c) Zn-D or Zn-Z
d) Zn-Zn
e) D-Y or Z-Y
f) D-Yn or Z-Yn
g)Zn-Y
h)Zn-Yn
i)Y-D or Y-Z
J)Y-Zn
k)Yn-D or Yn-Z
l)Yn-Zn
m)Y-Y
n)Y-Yn
o)Yn-Y
P)Yn-Yn
12. A method as claimed in claim 3 or any of claims 4 to 11 when dependent, directly or
indirectly upon claim 3, wherein the phase displacement of the transformer is calculated by
the following steps:
determining if the primary and secondary winding configurations are similar and if not
allocating a value of 1, otherwise allocating a value of 0;
determining a configuration result factor and adding a value according to the
configuration result factor to the value allocated in the previous step;
determining if the secondary winding of the transformer windings is reversed and if
not adding 6 to the value calculated in the previous step, otherwise leaving the value
unaltered; and
if the value is greater than 12 substracting 12, otherwise leaving the value unaltered,
thereby to determine the phase displacement of the transformer.
13. A method as claimed in claim 12, wherein the configuration result factor is determined

as follows:
during energisation of each pair of input terminals shorting the remaining terminal to
the low end of the energising power supply noting the pair of output terminals across which
the lowest output is measured and allocating a value depending on at which pair of output
terminals the lowest output is measured, said value also depending upon whether or not the
primary and secondary winding configurations are similar or not and naming the three values
allocated to obtain the configuration result factor.
14. A method as claimed in claim 12 or 13, wherein to determine if the secondary
windings of the transformer are reversed the transformer is energised phase to phase on the
primary and a corresponding phase to phase measurement made on the secondary and
measuring the phase shift and the primary with respect to the secondary.
15. Apparatus for characterising a three phase transformer comprising:
a single phase power supply;
means for selectively applying power from said power supply to pairs of input
terminals of a three phase transformer;
means for measuring the voltage between pairs of output terminals of a three phase
transformer and a control means comprising a processing means, said control means being
operative to control said power supply, means for measuring voltages and processing means
thereby to characterise a transformer.
16. Apparatus as claimed in claim 15, wherein there is provided a phase meter under
control of the control means.
17. Apparatus as claimed in claim 16 or 17, wherein the control means comprises a
programmed computer.



ABSTRACT


METHOD AND APPARATUS FOR CHARACTERISING A THREE PHASE
TRANSFORMER USING A SINGLE PHASE POWER SUPPLY
A method and apparatus for characterising a three phase transformer (3) using a single phase
power supply (1). Pairs of input terminals (H0-H3) of the transformer are sequentially
energised for each energisation and the voltage between pairs of output terminals (x0-x3) of
the transformer are measured. Measured voltages are processed in order to characterise the
winding configuration of the transformer. Either simultaneously or subsequently the presence
of neutrals on the primary and/or secondary side of the transformer are identified to enable the
winding configuration to be further characterised. Subsequently any phase displacement of
the transformer is determined. The apparatus comprises means (2) for selectively applying a
single phase power supply (1) to pairs of terminals (H0-H3) on the transformer (3) and for
measuring voltages between pairs of terminals (x0-x3) of the transformer and for measuring
phase difference between the primary and secondary sides of the transformer all under
automatic control of a control means (13) which includes a processing means to process
measured voltages and phase differences in order to characterise the transformer.

Documents:

02653--kolnp-2006-abstract.pdf

02653--kolnp-2006-claims.pdf

02653--kolnp-2006-correspondence others.pdf

02653--kolnp-2006-description(complete).pdf

02653--kolnp-2006-drawings.pdf

02653--kolnp-2006-form-1.pdf

02653--kolnp-2006-form-3.pdf

02653--kolnp-2006-form-5.pdf

02653--kolnp-2006-international publication.pdf

02653--kolnp-2006-international search authority report.pdf

02653--kolnp-2006-pct others.pdf

02653-kolnp-2006-correspondence others-1.1.pdf

02653-kolnp-2006-form-3-1.1.pdf

02653-kolnp-2006-gpa.pdf

2653-KOLNP-2006-(10-04-2012)-ABSTRACT.pdf

2653-KOLNP-2006-(10-04-2012)-AMANDED CLAIMS.pdf

2653-KOLNP-2006-(10-04-2012)-DESCRIPTION (COMPLETE).pdf

2653-KOLNP-2006-(10-04-2012)-DRAWINGS.pdf

2653-KOLNP-2006-(10-04-2012)-EXAMINATION REPORT REPLY RECEIVED.pdf

2653-KOLNP-2006-(10-04-2012)-FORM-1.pdf

2653-KOLNP-2006-(10-04-2012)-FORM-3.pdf

2653-KOLNP-2006-(10-04-2012)-PA-CERTIFIED COPIES.pdf

2653-KOLNP-2006-(10-04-2012)-PETITION UNDER RULE 137.pdf

2653-KOLNP-2006-(18-10-2013)-CORRESPONDENCE.pdf

2653-KOLNP-2006-(18-10-2013)-OTHERS.pdf

2653-KOLNP-2006-(21-11-2011)-CORRESPONDENCE.pdf

2653-KOLNP-2006-(21-11-2011)-OTHER DOCUMENT.pdf

2653-KOLNP-2006-(25-07-2013)-CORRESPONDENCE.pdf

2653-kolnp-2006-ASSIGNMENT.pdf

2653-kolnp-2006-CANCELLED PAGES.pdf

2653-KOLNP-2006-CORRESPONDENCE-1.1.PDF

2653-kolnp-2006-CORRESPONDENCE.pdf

2653-kolnp-2006-EXAMINATION REPORT.pdf

2653-kolnp-2006-form 18.pdf

2653-KOLNP-2006-FORM 2.pdf

2653-kolnp-2006-GPA.pdf

2653-kolnp-2006-GRANTED-ABSTRACT.pdf

2653-kolnp-2006-GRANTED-CLAIMS.pdf

2653-kolnp-2006-GRANTED-DESCRIPTION (COMPLETE).pdf

2653-kolnp-2006-GRANTED-DRAWINGS.pdf

2653-kolnp-2006-GRANTED-FORM 1.pdf

2653-kolnp-2006-GRANTED-FORM 2.pdf

2653-kolnp-2006-GRANTED-FORM 3.pdf

2653-kolnp-2006-GRANTED-FORM 5.pdf

2653-kolnp-2006-GRANTED-SPECIFICATION-COMPLETE.pdf

2653-KOLNP-2006-MISCLLENIOUS.pdf

2653-kolnp-2006-OTHERS.pdf

abstract-02653-kolnp-2006.jpg


Patent Number 260059
Indian Patent Application Number 2653/KOLNP/2006
PG Journal Number 14/2014
Publication Date 04-Apr-2014
Grant Date 31-Mar-2014
Date of Filing 13-Sep-2006
Name of Patentee HUBBELL LIMITED
Applicant Address 160 ALDERSGATE STREET,LONDON EC1A 4DD
Inventors:
# Inventor's Name Inventor's Address
1 FAWCETT,TIMOTHY,JAMES THE WHITE HOUSE,MAIN STREET,YOXALL EAST STAFFS,DE 13 8 NQ
PCT International Classification Number G01R31/06;G01R31/02
PCT International Application Number PCT/GB2005/000810
PCT International Filing date 2005-03-03
PCT Conventions:
# PCT Application Number Date of Convention Priority Country
1 0404918.5 2004-03-04 U.K.