Title of Invention

A NOVEL SYSTEM FOR DETECTION AND CLASSIFICATION OF POWER SYSTEM TRANSMISSION LINE FAULTS

Abstract Conventional electromechanical or solid state relays suffered from inflexibility, duplication efforts, complexity and cost. The present invention relates to a novel system for detection and classification of transmission line faults characterized in that the said system (i) a 3-phase variac (1) is connected to the main supply; (ii) output of (i) is connected to a 3-phase isolation transformer (2) of output whereof is connected to 100 km line model (3) which in turn is connected to star connected load of 10W per phase, the said model (3) having a mechanical fault creation arrangement with jumper cable to create type as well as location of faults at every 10 km ; (iii) switching circuit (4) connected to (3) to create a desired fault inception angle; (iv) data acquision card is connected between (3) and high speed computer (6); (v) computer monitor (6) displays the type and location of fault with the help of (5), employing LABVIEW software.
Full Text

The present invention relates to a novel system for detection
and classification of power/transmission line faults. More
particularly this invention pertains to a digital relay based on
frequency domain approach for detection and classification of
power system transmission line faults employing wavelet multi
resolution analysis (hereinafter referred to as *MRA/ for the
sake of brevity) to overcome the difficulties associated with
conventional voltage and current-based measurements due to the
effect of factors like, inter alia, fault inception angle, fault
impedance and fault distance. The wavelet transform devised and
effectively applied in the novel system of the subject invention
captures the dynamic characteristics of the non-stationary
transient fault signals using wavelet MRA coefficients, thereby
enabling a transmission line of 100 km in length representing the
EHV transmission, wherein by application of software developed
for this purpose in accordance with this invention it has been
possible to detect and classify accurately the different types of
power system faults.
Earlier electromechanical relays were used for transmission
line protection. These had several drawbacks such as high burden
on instrument transformers, longer operating time, contact
problems, etc. Solid-state relays which avoid most of these
difficulties were gradually replacing electromagneting relays.
Though successfully used, these suffer from a number of
disadvantages like inflexibility, duplication of specification
efforts, and inadaptability to changing system conditions,
complexity and cost. Software (digital) scheme avoid most of
these difficulties. Programmable equipment can respond faster

and may be used to implement complex threshold characteristics at
low cost. They can also be self-checking in nature thereby
requiring less maintenance and providing greater reliability.
Conventional relaying scheme usually work based on the
magnitudes of current signals where the fundamental component of
fault currents in time-domain is compared with the preset nominal
values. Hence these relays fail to operate during fault currents
with low magnitudes. On the other hand, frequency domain analysis
of fault currents checks for the presence of harmonics in current
waveforms which appear during fault conditions due to abrupt
change of current magnitude. Thus, by applying frequency domain
analysis, faults can be easily detected and classified even in
cases of low fault current in case of arcing faults, where
conventional relays fail to operate. Many of the fault
classification algorithms are mostly developed for shunt faults
having low impedance (non-arcing faults). But distance relays
fail to operate during high impedance faults due to under reach.
As the transient disturbances are quite low during high impedance
faults, relays based on current measurements do not distinguish
the fault conditions from normal conditions as the fault current
will not be considerably high.
The present invention aims at overcoming the difficulties
envisaged in the conventional methods.
The principal object of this invention is to provide a novel
system for detection and classification of power transmission
line faults.

A further object of this invention is to develop an algorithm for detection and
classification of transmission line faults using wavelet MRA with Daubechies-four (referred
to herein as Db-4) wavelet based on measurements and comparison of sharp variation in the
values of the currents for the three phases in the sixth stage MRA detail signals extracted
from the original line faults and read on the host computer with monitor.
A still further object of this invention is to provide a system using an algorithm in
conjunction with components/equipments which takes into account the effects of factors
like fault inception angle, fault impedance and fault distance while detecting and classifying
the nature of transmission line fault(s).
Another object of this invention is to provide a system using an algorithm based on
wavelet transform capable of capturing dynamic characteristics of non-stationary signal
using short-data window, efficiently analyzing the signals having transients or discontinuities,
e.g. the post-fault voltage/current waveform.
The foregoing objects are achieved by the present invention which relates to a novel
system for detection and classification of a novel system for detection and classification of
power system transmission line faults having the undernoted principal components -
(a) power supply source, (b) a transmission line model for 100 km length including 10 watts
per phase load, (c) switching circuit for incorporating fault inception angle (FIS), (d) data
acquisition system and digital cathode ray oscilloscope (CRO) and (e) computer, character-
ized in that -
(i) a three phase variac [ rating: 440V / 0 - 470V, 50 Hz ] is connected to the three
phase main supply;
(ii) output of three phase variac is connected to 3-phase isolation transformer
[ rating: 440V / 20V (line to line voltage) and 180 VA ];
(iii) output of the isolation transformer is connected to the 100 km transmission line
model;

(v) presence of star connected 1 Ow bulb load (per phase) causes the current to pass
from 0 km to 100 km of the transmission line model; and
(vi) the DAQ card and digital CRO monitor the three phase currents at the Oth km
of the transmission line model.
Brief theoretical background of the invention :
The continuous WT (CWT) of a signal x (t) is defined as -
I
where l//(t) is the mother wavelet and other wavelets
are its dilated and translated versions, a and b are the dilation parameter and the translation
parameters respectively. In general, the mother wavelet is compactly supported in both time-
domain and frequency-domain, which, together with the dilation and translation operations,
provides variable time-frequency resolution ability for different frequencies.
The discrete WT (DWT), instead of CWT, is always used in practice. For a signal x (t),
its DWT coefficient with respect to a discrete weavelet y/mn can be represented by

where is defined by

For some special choices of If/, aQ and bQ, {lf/ma, m,n eZ} constitute an orthonormal
basis of L2 (i?) (the space of finite-energy functions). The most frequently used selections are
a0 =2 and b0 = 1. A signal x (t) can then be represented by its DWT coefficients as


The function, Iff (t) itself is called the mother wavelet
which in this case is the Db-4 wavelet. The output of the DWT
consists of the remaining "approximation" components, and all of
the accumulated "detail" components.
The actual implementation of DWT is done by multi-resolution
analysis (MRA). By using MRA a signal can be analyzed at different
frequency bands with different resolutions. The signal to be
analyzed is decomposed into a smooth approximation and a detail.
The approximation is further decomposed into an approximation
and detail and the process is repeated. The decomposition of the
signal is obtained by successive high pass and low pass filtering
of the time domain signal. The successive stages of decomposition
are known as levels and the above procedure is known as sub-band
coding. The approximation and details at level-1 and level-2 have
been represented using suffixes al and a2. The MRA details at
various levels contain the features for detection and classification
of faults.
Owing to the unique feature of providing multi-resolution
both in time and frequency by wavelets, the sub-band information
can be extracted from the original signal. Thus for transmission
line fault analysis in a power system, applied to faults, these
sub-band informations are seen to provide useful clues regarding
the faults for their classification in an elegant way. The
generated time domain signal for each case is analyzed using
Wavelet transform. Amongst different decomposed levels, only 6th
level detail coefficients of current signals is considered for
the analysis, because the absolute values of the summation of 6th
level detail coefficients of current signals for all inception

angles considered for the analysis are found to be higher as
compared to those from other level output. It indicates that
total area under the characteristics of 6th level outputs is more
than that of other level outputs. Another reason for the 6th
level output to be selected as the parameter for fault
classification is that the summation of 6th level detail
coefficients of current signals satisfies the characteristic
relationships for all types of faults for classification purposes.
Thus based on sixth level detail coefficients of current signals,
an efficient generalized algorithm for fault classification based
on the Wavelet analysis is depicted below.
The transmission line faults in a power system are usually
classified as single line to ground (L-G), double line to ground
(L-L-G), double line (L-L), and 3 phase symmetrical (L-L-L) and
(L-L-L-G) faults. The fault inception angle has a considerable
effect on the phase current samples and therefore also on wavelet
transforms output of post-fault signals as confirmed from several
simulation studies. As the waves are periodic, it is sufficient
to study the effect of inception angle in the range of 0° to 180°.
The algorithm proceeds as follows :
Let S , S. and S be the summation of sixth level detail
a a c
coefficients values for current in phases a, b and c, respectively.
When the summation of S , Sw and S is equal to zero, then the
a' b c ^
fault can be either L-L-L or L-L fault. The discrimination
between these two types of faults is based on the fact that the
magnitudes of Sa, Sb and S are comparable to each other. In case
of L-L fault, the addition of any two phases summations namely,
either S +S. or SK+S„ or S +S tends to nearly equal to zero and

remaining phase summation coefficient is very small and almost
negligible compared to other two summations having equal values
with opposite signs. If the above condition is not satisfied,
then it is considered as L-L-L fault.
When the summation of Sa, Sb and Sc is not equal to zero, then
it can be either L-G or L-L-G fault- If the absolute value of any
two coefficients is equal and always much smaller than the
absolute value of the remaining coefficients, then it is a L-G
fault. If the absolute value of any two coefficients is not equal
to zero and is always much higher than the absolute value of
remaining coefficients, then it is a L-L-G fault.
Sequence of steps for calculation of Sa, S^ and Sc :
The following steps are incorporated to obtain the wavele|t
summation coefficients S , S. and S„ :
a* o c
1. The fault currents of each phase are measured continuously.
2. These fault currents are then sampled with a sampling frequency
of 12.5 kHz.
3. These samples are then convolved with the low-pass filter
coefficients of sixth level Db-4 wavelet to obtain the
detail coefficients.
4. The obtained coefficients from the above step are summed up
to get the wavelet summation coefficients Sa, Sb and Sc for
the three phase currents la, lb and Ic, respectively.
The invention will now be described in more details with the
help of the illustrative drawings accompanying this specification

wherein -
Fig.lA shows one level decomposition diagram with real
signals;
Fig.IB depicts the 'fault classification algorithm' in
frequency domain;
Fig.2 (a) shows laboratory model of a 100 km 3 phase
transmission line;
Fig.2(b) illustrates the basic block for every 10km of
3 phase transmission line;
Fig.3 gives a block diagram of switching circuit;
Fig.4 is the block diagram representation for fault
classification in LABVIEW using wavelets;
Fig.5 (a) is the sub(VI) diagram for wavelet transform;
Fig.5(b) is the sub(VI) diagram for wavelet coefficient
calculation;
Fig.5(c) shows sub(VI) for fault classification for L-L-L
and L-L faults;
Fig.5(d) is sub(VI) for fault classification for L-G and
L-L-G faults;
Fig.6 shows the set up for real time fault analysis of
the transmission lines;
With regard Fig.lA, this is a schematic diagram of
'Approximation' and 'detailed' components on the basis of the
output of the DWT. As shown therein, the input current signal is
split into its high and low frequency components. Hence at the
sixth level, since the high frequency components fall in the
range of 97.65 Hz to 195.31 Hz within which the 2nd and 3rd order
harmonics lie, these co-efficients are considered for further

analysis.
As would be discussed in detail hereafter, the wavelet block
in LABVIEW software including classification algorithm shown
Fig.IB computes discrete wavelet transform and supports the
waveform data, taking into account the most used wavelets. The
output of this signal is made to pass another virtual instrument
(also referred to herein as VI for the sake of brevity) block
which in turn produces the wavelet coefficient. Fig.5(a) of the
drawings shows the LABVIEW implementation for computation of
S , S. and S„ of discrete wavelet detail coefficient for 6th level
a b c
for each of the three phase currents of transmission line.
Then the output is passed into another sub-program virtual
instrumentation [abbreciated herein as Sub-(VI)], as shown in
Fig.5(b) of the drawings for calculation of wavelet co-efficients
for one phase and it is same for remaining two phases for
generating wavelet co-efficients.
IMPLEMENTATION OF CLASSIFICATION ALGORITHM
USING LABVIEW SOFTWARE OF THIS INVENTION
(i) Modelling of Transmission Lines
A transmission line was modelled keeping in view the actual
existing lines of 400KV. The main concept involved in modeling
was to keep the p.u. (Per Unit) values similar and expressing
with respect to a common base voltage and base KVA. At first the
p.u. values of model transmission lines was determined and with
help of those values and base impedance of actual system, L and

C were determined for actual system. The values of L and C were
checked with that of recorded values of actual system.
Model line parameters :
Base Voltage - 20V
Base VA = 180VA
Base Current = 5Amp
Length designed for = lOOKm
■*" Positive and Negative sequence parameters (per lOKm) :
Resistance = 0.17 Q Inductance = 0.13195 mH
Capacitance » 8.936 |iF
w Negative sequence parameters (per lOKm) :
Resistance = 0.08 Q Inductance = 0.4510 mH
Capacitance = 6.09 jiF
(ii) Three Phase Transmission Line Model - Please see Figs. 2(a)
and 2(b) of the drawings.
The basic scheme employs a lOOKm transmission line as
shown in Figure 2(a) which consists of ten basic blocks shown in
Figure 2(b). It is connected through isolating transformer which
steps down to 440/20 volts supply, 50 Hz at one end meant to serve
as sending end. The model line is rated at 5 Amps.
At receiving end of line resistive load of around 10W (per

phase) is connected.
Faults are applied at the terminals of any module by means
of switching circuit. The switching circuit shown in Figure 3
creates fault at particular angle known as fault inception angle.
(iii) SWITCHING CIRCUIT
Faults transient studies of electrical systems require
simulation of system voltage which starts its waveform from a
fixed value of phase angle. Thus real time study of such system
becomes difficult in mini models, network analysers and without
the help of a switching unit which can control the starting point
of the voltage waveform.
A signal generator or frequency multiplier is used to permit
one degree resolution of switching angle selector. This produces
a frequency of 360f, where f is the base frequency of signal
waveform that needs switching.
One complete cycle = 360 degrees
Frequency - 50Hz
Thus a frequency of 360 X 50 = 18KHz permits one degree
resolution of switching angle selector.
Thus every successive zero crossing of high frequency wave
corresponds to one degree angle interval of the base signal. Thus
the angle sensing becomes independent of reference signal frequency.
So a high frequency digital counter counts the number of zero

crossing of high frequency wave and with the help of decoder
circuit and decade switches, only a single pulse count is selected
at a time for thyristor or the IGBT firing instant- This totally
eliminates the possibility of wrong triggering for if the decoded
pulse count fails to trigger the IGBT's, no more triggering
signals are available for the control circuitry. A low frequency
counter counts pulses/sec and controls the duration of the on
condition of the equipment. The unit is put off by a separate
relay contact which is activated from the low frequency counter.
Both phase angle and duration control are performed by digital
counters which are reliable and independent of supply frequency
and voltage variations.
(iv) SOFTWARE IMPLEMENTATION USING LABVIEW - See Fig.4 of the
drawings.
(v) Wavelet Block
This computes discrete wavelet Transform and supports the
waveform data and includes the most used wavelets. This output of
this signal is made to pass into another VI block which is turn
produces the wavelet coefficient. The subVI(l) block diagrm is as
shown in Fig.5 (a) of the drawings and is also same for remaining
two phase.
The Figure 5(a) shows the LABVTEW implementation (sub VI
diagram) for computation of discrete waveform to be used in
wavelets. Then the output is passed into another Sub VI for
calculation of wavelet coefficients. The second Sub VI block
diagram of a phase is shown in Figure 5(b) and is same for

remaining two phases and it generates the wavelet coefficients.
The generated coefficients are checked whether their sum is
zero or not. If true, then the adder checks whether the sum of two
inputs is zero or not i.e. (Sa+Sb=0) or (Sb+Sc=0) or (Sc+Sa=0).
Then tolerance check is done to the adder output. If again true,
it will show L-L fault and if not then output is made to pass
through HOT blocks which computes the negation of the input. The
output signals are passed through merge block which merges two or
more signals into single output which shows the
L-L-L fault, Figure 5{c). But if the sum of coefficients is not
zero then absolute value of input is determined and compared with
another absolute value of other input i.e. |Sal = |Sbl and so on is
done. If the values are equal tolerance check is done and the
output is given as L-G fault or else it is L-L-G fault
fFigure 5(d)]. Correspondingly, across each faults bulbs are
placed and glowing of bulb represents the type of fault that has
occurred,,
REAL TIME IMPLEMENTATION OF FAULT DETECTION
AND CLASSIFICATION ALGORITHM
Fig. 6 of the drawings show the set up for real time fault
analysis of the transmission lines, wherein there is shown -
w Isolation transformer
w Transmission line block set
«•" Switching angle circuits
w* Data acquisition system

Experimental procedure :
The three isolating transformers were fed from three phase
variac and voltage was stepped down to 20V by isolating transformer
which is the input to the tranmission line block. A switching
circuit was used to create fault in the line. The fault inception
angle has a considerable effect on the phase current samples and
therefore several simulation studies were perform to obtain post
fault signals. The transmission line was connected to a balanced
load of 10W per phase and fault inception angle was selected by
setting the single pole ten way switch and at that particular
angle, a fault was created. The real time data acquisition was
done through data acquisition card which is a high performance
multifunctional analog to digital Input/Output board for Personal
Computer.
After the three current signals are acquired using data
acquisition card, they are passed through LABVIEW program as
shown in the Fig.4. After acquisition of the current signals, the
Sa, Sb and Sc are first calculated using LABVIEW software as shown
in the Fig.4 and then these values are used for classification
using the same LABVIEW program.
Wavelets provide the unique feature of providing multiple
resolutions both in time and frequency and hence the sub-band
information can be extracted from the original signal. Thus for
the transmission line fault analysis in power system, applied to
fault, these sub-band information has seen to provide useful
clues regarding the fault for their classification in an elegant
way. The generated time domain signals for each case is analyzed

using wavelet transform. Among the several decomposed levels
only the sixth level detail coefficients of current signals is
considered for analysis. This is because summation of sixth level
output satisfies the characteristic relationship of all types of
faults for classification purposes.
The wavelet algorithm was made to recognize the type of
fault occuring in the system. Corresponding to every type of
fault, there is one LED (light emitting diode) in the front panel
of LABVTEW software. When a particular fault occurs in the
system, then the signals are processed through the data acquisition
system to the computer and the algorithm analysis was done to the
inputted signal. Correspondingly one LED glows showing the type
of fault that has occurred. Simultaneously current and voltage
waveform of faulted phase and healthy phase was traced from the
computer.
Then in the hardware model a fault was created at about 50Km
with a fault inception angle of 15°. The sigle pole 10 way switch
was selected at 15° manually for fault inception angle.
The currents were stepped down individually and then made to
pass through data acquisition card which converts analog signal
to digital signal. Then applying discrete wavelet transform to
the three acquired signals, it generates the Sa, Sb, Sc coefficients
which were displayed on the monitor. The coefficients were checked
accordingly to determine which type of fault was occurred.
For example if |sJ = |Scl & «Sa, it is an L-G fault involving
phase A. So when the condition was satisfied the corresponding

LED started to glow indicating the type of fault that has occurred
in the system. LABVTEW interpretation shows the type(s) of fault
occurred in the system.
The algorithm for fault classification reponded properly
when different types of fault were given to the transmission line
block.
Advantages
1. The system of this invention enables early detection of line
fault with consequent speedy restoration of power supply in
industrial as well as domestic sectors, particularly in the
former, thereby ensuring avoidance of financial loss.
2. Speedy recording of the events for the purpose of adopting
remedial measures for specific user industries by ascertaining
the nature of interruption.
As the present invention may be embodied in several forms
without departing from the spirit or essential characteristics
thereof, it should also be understood that the above described
examples and illustrations are not limited by any of the details
of the foregoing description, unless otherwise specified, but
rather should be construed broadly within its spirit and scope as
defined in the appended claims and, therefore, all changes and
modifications that fall within the meets and bounds of the
claims, or equivalences of such meets and bounds are intended to
be embraced by the appended claims.

We claim:
1. A novel system for detection and classification of power system transmission
line faults in which the principal components comprising;
(a)power supply source, (b)a transmission line model for 100 km length
including lOwatts per phase load, (c)switching circuit by which faults are
applied at the terminals of any module, (d)data acquisition system and digital
cathode ray oscilloscope (CRO) and (e) computer, wherein three phase variac
(1) is connected to three-phase isolation transformer (2) of which output is
connected to the 100 km transmission line model (3) and the said model (3)

having a mechanical fault creation arrangement to create type as well as
location of faults at every 10 km is connected to star connected load of 10 w
(3)per phase and switching circuit (4) as well as a three channel digital CRO are
connected to the transformer line model (3)to create a desired fault inception

,
angle (FIA) and between the transmission line model (3) and High speed
computer (6) data acquisition card (DAQ)(5) is connected and jumper cable for
creating faults,
Characterised in that wevelet captures the dynamic characteristics of the non-
stationary transient fault signals using wavelet MRA coefficients, thereby
enabling a transmission line of 100 km in length representing the EHV


transmission to detect and classify accurately the different types of power

system faults wherein data acquisition is carried out through data acquisition

card serving as a high performance multifunctional analogue to digital
input/output board for the said host computer.
2. A system as claimed in Claim 1, where in the sequence of operations is
conducted under fault conditions comprising.
(i) the switching circuit (4)is set at a particular angle, fault inception angle
(FIA)varying between 0 and 360 degrees;
(ii) main three phase supply is switched on;
(iii) three phase variac (1) is set at 440V, which is the input for the isolation
transformer (2);
(iv) an output voltage of 20V (line to line voltage) given by the isolation
transformer (2) is fed to the transmission line model (3);
(v) presence of star connected 10 w bulb load (per phase) causes the current to
pass from 0 km to 100 km of the transmission line model (3); and
(vi) the DAQ card (5)and digital CRO (5)monitor the three phase currents at the
0 th km of the transmission line model (3).
3. A system as claimed in Claims 1 and 2, in which shock hazard is eliminated
in the isolation transformer by grounding the secondary side neutral point and

the sub-band information can be extracted from the original signal due to multi-
resolution in time as well as in frequency by wavelet.
4. A system as claimed in Claims land 2, in which values per unit (p.u) of 400
KV transmission lines of 100 km length are kept similar and expressed with
respect to a common base voltage and base KVA, and with the p.u. values and
base inpedance of actual system, inductance L and capacitance are
determined for the actual system, employing (i)model line parameters,
ii)positive and negative sequence parameters (per 10Km)and (iii)zero sequence
parameters as under:
Model line parameters:
Base Voltage = 20V
BaseVA=180VA
Base Current = 5 Amp
Length designed for = 100Km
Positive and Negative sequence parameters (per 10 Km)
Resistance(R1) = 0.17 Q
Inductance(L1) = 0.13195 mH
. Capacitance(C1) = 8.936 µF

Zero sequence parameters (per 10 Km)
Resistance(Ro) = 0.08 Ω
Inductance(Lo)= 0.4510 mH.
Capacitance(Co) = 6.09 µF
and the said transmission line consisting often basic blocks are connected
through isolation transformer (2)which steps down the line voltage from 440
. volts to 20 volts at 50Hz ait one end serving as the sending end, current rating of
the line being 5 ampere, and at the receiving end of line, there is connected a
resistive load of 10 W per phase.
5. A novel system for detection and classification of power system transmission
line faults, substantially as hereinbefore described with particular reference to
the accompanying drawings.



Abstract


Title - "A novel system for detection and classification
of power system transmission line faults."
Conventional electromechanical or solid state relays suffered from inflexibility,
duplication efforts, complexity and cost.
The present invention relates to a novel system for detection and classification of
transmission line faults characterized in that the said system
(i) a 3-phase variac (1) is connected to the main supply;
(ii) output of (i) is connected to a 3-phase isolation transformer (2) of output
whereof is connected to 100 km line model (3) which in turn is connected to
star connected load of 10W per phase, the said model (3) having a mechanical
fault creation arrangement with jumper cable to create type as well as location
of faults at every 10 km ;
(iii) switching circuit (4) connected to (3) to create a desired fault inception angle;
(iv) data acquision card is connected between (3) and high speed computer (6);
(v) computer monitor (6) displays the type and location of fault with the help
of (5), employing LABVIEW software.

Documents:

00611-kol-2008-abstract.pdf

00611-kol-2008-claims.pdf

00611-kol-2008-correspondence others.pdf

00611-kol-2008-description complete.pdf

00611-kol-2008-drawings.pdf

00611-kol-2008-form 1.pdf

00611-kol-2008-form 2.pdf

00611-kol-2008-form 3.pdf

00611-kol-2008-pa.pdf

611-KOL-2008-(06-11-2012)-CLAIMS.pdf

611-KOL-2008-(06-11-2012)-CORRESPONDENCE.pdf

611-KOL-2008-(06-11-2012)-FORM-2.pdf

611-KOL-2008-(06-11-2012)-OTHERS.pdf

611-KOL-2008-(09-12-2011)-ABSTRACT.pdf

611-KOL-2008-(09-12-2011)-AMANDED CLAIMS.pdf

611-KOL-2008-(09-12-2011)-AMANDED PAGES OF SPECIFICATION.pdf

611-KOL-2008-(09-12-2011)-DESCRIPTION (COMPLETE).pdf

611-KOL-2008-(09-12-2011)-DRAWINGS.pdf

611-KOL-2008-(09-12-2011)-EXAMINATION REPORT REPLY RECEIVED.pdf

611-KOL-2008-(09-12-2011)-FORM-1.pdf

611-KOL-2008-(09-12-2011)-FORM-2.pdf

611-KOL-2008-(09-12-2011)-OTHERS.pdf

611-KOL-2008-(30-10-2012)-PA.pdf

611-KOL-2008-ARGUMENTS.pdf

611-KOL-2008-CANCELLED PAGES.pdf

611-KOL-2008-CORRESPONDENCE.pdf

611-KOL-2008-EXAMINATION REPORT.pdf

611-KOL-2008-GRANTED-ABSTRACT.pdf

611-KOL-2008-GRANTED-CLAIMS.pdf

611-KOL-2008-GRANTED-DESCRIPTION (COMPLETE).pdf

611-KOL-2008-GRANTED-DRAWINGS.pdf

611-KOL-2008-GRANTED-FORM 1.pdf

611-KOL-2008-GRANTED-FORM 2.pdf

611-KOL-2008-GRANTED-FORM 3.pdf

611-KOL-2008-GRANTED-SPECIFICATION-COMPLETE.pdf

611-KOL-2008-PA.pdf

611-KOL-2008-PETITION UNDER RULE 137.pdf

611-KOL-2008-REPLY TO EXAMINATION REPORT.pdf

abstract-00611-kol-2008 fig 1.jpg

abstract-00611-kol-2008 fig 2.jpg


Patent Number 256209
Indian Patent Application Number 611/KOL/2008
PG Journal Number 20/2013
Publication Date 17-May-2013
Grant Date 16-May-2013
Date of Filing 27-Mar-2008
Name of Patentee BIRLA INSTITUTE OF TECHNOLOGY
Applicant Address P.O. MESRA, RANCHI
Inventors:
# Inventor's Name Inventor's Address
1 M. JAYABHARATA REDDY LECTURER, DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING, BIRLA INSTITUTE OF TECHNOLOGY (DEEMED UNIVERSITY) MESRA, RANCHI-835215
2 DR. D. K. MOHANTA READER, DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING, BIRLA INSTITUTE OF TECHNOLOGY (DEEMED UNIVERSITY) MESRA, RANCHI-835215
PCT International Classification Number H02H7/26
PCT International Application Number N/A
PCT International Filing date
PCT Conventions:
# PCT Application Number Date of Convention Priority Country
1 NA